# Modbus Input Plugin
|
||
|
|
||
|
This plugin collects data from [Modbus][modbus] registers using e.g. Modbus TCP
|
||
|
or serial interfaces with Modbus RTU or Modbus ASCII.
|
||
|
|
||
|
⭐ Telegraf v1.14.0
|
||
|
🏷️ iot
|
||
|
💻 all
|
||
|
|
||
|
[modbus]: https://www.modbus.org/
|
||
|
|
||
|
## Global configuration options <!-- @/docs/includes/plugin_config.md -->
|
||
|
|
||
|
In addition to the plugin-specific configuration settings, plugins support
|
||
|
additional global and plugin configuration settings. These settings are used to
|
||
|
modify metrics, tags, and field or create aliases and configure ordering, etc.
|
||
|
See the [CONFIGURATION.md][CONFIGURATION.md] for more details.
|
||
|
|
||
|
[CONFIGURATION.md]: ../../../docs/CONFIGURATION.md#plugins
|
||
|
|
||
|
## Configuration
|
||
|
|
||
|
```toml @sample_general_begin.conf @sample_register.conf @sample_request.conf @sample_metric.conf @sample_general_end.conf
|
||
|
# Retrieve data from MODBUS slave devices
|
||
|
[[inputs.modbus]]
|
||
|
## Connection Configuration
|
||
|
##
|
||
|
## The plugin supports connections to PLCs via MODBUS/TCP, RTU over TCP, ASCII over TCP or
|
||
|
## via serial line communication in binary (RTU) or readable (ASCII) encoding
|
||
|
##
|
||
|
## Device name
|
||
|
name = "Device"
|
||
|
|
||
|
## Slave ID - addresses a MODBUS device on the bus
|
||
|
## Range: 0 - 255 [0 = broadcast; 248 - 255 = reserved]
|
||
|
slave_id = 1
|
||
|
|
||
|
## Timeout for each request
|
||
|
timeout = "1s"
|
||
|
|
||
|
## Maximum number of retries and the time to wait between retries
|
||
|
## when a slave-device is busy.
|
||
|
# busy_retries = 0
|
||
|
# busy_retries_wait = "100ms"
|
||
|
|
||
|
# TCP - connect via Modbus/TCP
|
||
|
controller = "tcp://localhost:502"
|
||
|
|
||
|
## Serial (RS485; RS232)
|
||
|
## For RS485 specific setting check the end of the configuration.
|
||
|
## For unix-like operating systems use:
|
||
|
# controller = "file:///dev/ttyUSB0"
|
||
|
## For Windows operating systems use:
|
||
|
# controller = "COM1"
|
||
|
# baud_rate = 9600
|
||
|
# data_bits = 8
|
||
|
# parity = "N"
|
||
|
# stop_bits = 1
|
||
|
|
||
|
## Transmission mode for Modbus packets depending on the controller type.
|
||
|
## For Modbus over TCP you can choose between "TCP" , "RTUoverTCP" and
|
||
|
## "ASCIIoverTCP".
|
||
|
## For Serial controllers you can choose between "RTU" and "ASCII".
|
||
|
## By default this is set to "auto" selecting "TCP" for ModbusTCP connections
|
||
|
## and "RTU" for serial connections.
|
||
|
# transmission_mode = "auto"
|
||
|
|
||
|
## Trace the connection to the modbus device
|
||
|
# log_level = "trace"
|
||
|
|
||
|
## Define the configuration schema
|
||
|
## |---register -- define fields per register type in the original style (only supports one slave ID)
|
||
|
## |---request -- define fields on a requests base
|
||
|
## |---metric -- define fields on a metric base
|
||
|
configuration_type = "register"
|
||
|
|
||
|
## Exclude the register type tag
|
||
|
## Please note, this will also influence the grouping of metrics as you won't
|
||
|
## see one metric per register type anymore!
|
||
|
# exclude_register_type_tag = false
|
||
|
|
||
|
## --- "register" configuration style ---
|
||
|
|
||
|
## Measurements
|
||
|
##
|
||
|
|
||
|
## Digital Variables, Discrete Inputs and Coils
|
||
|
## measurement - the (optional) measurement name, defaults to "modbus"
|
||
|
## name - the variable name
|
||
|
## data_type - the (optional) output type, can be BOOL or UINT16 (default)
|
||
|
## address - variable address
|
||
|
|
||
|
discrete_inputs = [
|
||
|
{ name = "start", address = [0]},
|
||
|
{ name = "stop", address = [1]},
|
||
|
{ name = "reset", address = [2]},
|
||
|
{ name = "emergency_stop", address = [3]},
|
||
|
]
|
||
|
coils = [
|
||
|
{ name = "motor1_run", address = [0]},
|
||
|
{ name = "motor1_jog", address = [1]},
|
||
|
{ name = "motor1_stop", address = [2]},
|
||
|
]
|
||
|
|
||
|
## Analog Variables, Input Registers and Holding Registers
|
||
|
## measurement - the (optional) measurement name, defaults to "modbus"
|
||
|
## name - the variable name
|
||
|
## byte_order - the ordering of bytes
|
||
|
## |---AB, ABCD - Big Endian
|
||
|
## |---BA, DCBA - Little Endian
|
||
|
## |---BADC - Mid-Big Endian
|
||
|
## |---CDAB - Mid-Little Endian
|
||
|
## data_type - BIT (single bit of a register)
|
||
|
## INT8L, INT8H, UINT8L, UINT8H (low and high byte variants)
|
||
|
## INT16, UINT16, INT32, UINT32, INT64, UINT64,
|
||
|
## FLOAT16-IEEE, FLOAT32-IEEE, FLOAT64-IEEE (IEEE 754 binary representation)
|
||
|
## FIXED, UFIXED (fixed-point representation on input)
|
||
|
## STRING (byte-sequence converted to string)
|
||
|
## bit - (optional) bit of the register, ONLY valid for BIT type
|
||
|
## scale - the final numeric variable representation
|
||
|
## address - variable address
|
||
|
|
||
|
holding_registers = [
|
||
|
{ name = "power_factor", byte_order = "AB", data_type = "FIXED", scale=0.01, address = [8]},
|
||
|
{ name = "voltage", byte_order = "AB", data_type = "FIXED", scale=0.1, address = [0]},
|
||
|
{ name = "energy", byte_order = "ABCD", data_type = "FIXED", scale=0.001, address = [5,6]},
|
||
|
{ name = "current", byte_order = "ABCD", data_type = "FIXED", scale=0.001, address = [1,2]},
|
||
|
{ name = "frequency", byte_order = "AB", data_type = "UFIXED", scale=0.1, address = [7]},
|
||
|
{ name = "power", byte_order = "ABCD", data_type = "UFIXED", scale=0.1, address = [3,4]},
|
||
|
{ name = "firmware", byte_order = "AB", data_type = "STRING", address = [5, 6, 7, 8, 9, 10, 11, 12]},
|
||
|
]
|
||
|
input_registers = [
|
||
|
{ name = "tank_level", byte_order = "AB", data_type = "INT16", scale=1.0, address = [0]},
|
||
|
{ name = "tank_ph", byte_order = "AB", data_type = "INT16", scale=1.0, address = [1]},
|
||
|
{ name = "pump1_speed", byte_order = "ABCD", data_type = "INT32", scale=1.0, address = [3,4]},
|
||
|
]
|
||
|
|
||
|
## --- "request" configuration style ---
|
||
|
|
||
|
## Per request definition
|
||
|
##
|
||
|
|
||
|
## Define a request sent to the device
|
||
|
## Multiple of those requests can be defined. Data will be collated into metrics at the end of data collection.
|
||
|
[[inputs.modbus.request]]
|
||
|
## ID of the modbus slave device to query.
|
||
|
## If you need to query multiple slave-devices, create several "request" definitions.
|
||
|
slave_id = 1
|
||
|
|
||
|
## Byte order of the data.
|
||
|
## |---ABCD -- Big Endian (Motorola)
|
||
|
## |---DCBA -- Little Endian (Intel)
|
||
|
## |---BADC -- Big Endian with byte swap
|
||
|
## |---CDAB -- Little Endian with byte swap
|
||
|
byte_order = "ABCD"
|
||
|
|
||
|
## Type of the register for the request
|
||
|
## Can be "coil", "discrete", "holding" or "input"
|
||
|
register = "coil"
|
||
|
|
||
|
## Name of the measurement.
|
||
|
## Can be overridden by the individual field definitions. Defaults to "modbus"
|
||
|
# measurement = "modbus"
|
||
|
|
||
|
## Request optimization algorithm.
|
||
|
## |---none -- Do not perform any optimization and use the given layout(default)
|
||
|
## |---shrink -- Shrink requests to actually requested fields
|
||
|
## | by stripping leading and trailing omits
|
||
|
## |---rearrange -- Rearrange request boundaries within consecutive address ranges
|
||
|
## | to reduce the number of requested registers by keeping
|
||
|
## | the number of requests.
|
||
|
## |---max_insert -- Rearrange request keeping the number of extra fields below the value
|
||
|
## provided in "optimization_max_register_fill". It is not necessary to define 'omitted'
|
||
|
## fields as the optimisation will add such field only where needed.
|
||
|
# optimization = "none"
|
||
|
|
||
|
## Maximum number register the optimizer is allowed to insert between two fields to
|
||
|
## save requests.
|
||
|
## This option is only used for the 'max_insert' optimization strategy.
|
||
|
## NOTE: All omitted fields are ignored, so this option denotes the effective hole
|
||
|
## size to fill.
|
||
|
# optimization_max_register_fill = 50
|
||
|
|
||
|
## Field definitions
|
||
|
## Analog Variables, Input Registers and Holding Registers
|
||
|
## address - address of the register to query. For coil and discrete inputs this is the bit address.
|
||
|
## name *1 - field name
|
||
|
## type *1,2 - type of the modbus field, can be
|
||
|
## BIT (single bit of a register)
|
||
|
## INT8L, INT8H, UINT8L, UINT8H (low and high byte variants)
|
||
|
## INT16, UINT16, INT32, UINT32, INT64, UINT64 and
|
||
|
## FLOAT16, FLOAT32, FLOAT64 (IEEE 754 binary representation)
|
||
|
## STRING (byte-sequence converted to string)
|
||
|
## length *1,2 - (optional) number of registers, ONLY valid for STRING type
|
||
|
## bit *1,2 - (optional) bit of the register, ONLY valid for BIT type
|
||
|
## scale *1,2,4 - (optional) factor to scale the variable with
|
||
|
## output *1,3,4 - (optional) type of resulting field, can be INT64, UINT64 or FLOAT64.
|
||
|
## Defaults to FLOAT64 for numeric fields if "scale" is provided.
|
||
|
## Otherwise the input "type" class is used (e.g. INT* -> INT64).
|
||
|
## measurement *1 - (optional) measurement name, defaults to the setting of the request
|
||
|
## omit - (optional) omit this field. Useful to leave out single values when querying many registers
|
||
|
## with a single request. Defaults to "false".
|
||
|
##
|
||
|
## *1: These fields are ignored if field is omitted ("omit"=true)
|
||
|
## *2: These fields are ignored for both "coil" and "discrete"-input type of registers.
|
||
|
## *3: This field can only be "UINT16" or "BOOL" if specified for both "coil"
|
||
|
## and "discrete"-input type of registers. By default the fields are
|
||
|
## output as zero or one in UINT16 format unless "BOOL" is used.
|
||
|
## *4: These fields cannot be used with "STRING"-type fields.
|
||
|
|
||
|
## Coil / discrete input example
|
||
|
fields = [
|
||
|
{ address=0, name="motor1_run" },
|
||
|
{ address=1, name="jog", measurement="motor" },
|
||
|
{ address=2, name="motor1_stop", omit=true },
|
||
|
{ address=3, name="motor1_overheating", output="BOOL" },
|
||
|
{ address=4, name="firmware", type="STRING", length=8 },
|
||
|
]
|
||
|
|
||
|
[inputs.modbus.request.tags]
|
||
|
machine = "impresser"
|
||
|
location = "main building"
|
||
|
|
||
|
[[inputs.modbus.request]]
|
||
|
## Holding example
|
||
|
## All of those examples will result in FLOAT64 field outputs
|
||
|
slave_id = 1
|
||
|
byte_order = "DCBA"
|
||
|
register = "holding"
|
||
|
fields = [
|
||
|
{ address=0, name="voltage", type="INT16", scale=0.1 },
|
||
|
{ address=1, name="current", type="INT32", scale=0.001 },
|
||
|
{ address=3, name="power", type="UINT32", omit=true },
|
||
|
{ address=5, name="energy", type="FLOAT32", scale=0.001, measurement="W" },
|
||
|
{ address=7, name="frequency", type="UINT32", scale=0.1 },
|
||
|
{ address=8, name="power_factor", type="INT64", scale=0.01 },
|
||
|
]
|
||
|
|
||
|
[inputs.modbus.request.tags]
|
||
|
machine = "impresser"
|
||
|
location = "main building"
|
||
|
|
||
|
[[inputs.modbus.request]]
|
||
|
## Input example with type conversions
|
||
|
slave_id = 1
|
||
|
byte_order = "ABCD"
|
||
|
register = "input"
|
||
|
fields = [
|
||
|
{ address=0, name="rpm", type="INT16" }, # will result in INT64 field
|
||
|
{ address=1, name="temperature", type="INT16", scale=0.1 }, # will result in FLOAT64 field
|
||
|
{ address=2, name="force", type="INT32", output="FLOAT64" }, # will result in FLOAT64 field
|
||
|
{ address=4, name="hours", type="UINT32" }, # will result in UIN64 field
|
||
|
]
|
||
|
|
||
|
[inputs.modbus.request.tags]
|
||
|
machine = "impresser"
|
||
|
location = "main building"
|
||
|
|
||
|
## --- "metric" configuration style ---
|
||
|
|
||
|
## Per metric definition
|
||
|
##
|
||
|
|
||
|
## Request optimization algorithm across metrics
|
||
|
## |---none -- Do not perform any optimization and just group requests
|
||
|
## | within metrics (default)
|
||
|
## |---max_insert -- Collate registers across all defined metrics and fill in
|
||
|
## holes to optimize the number of requests.
|
||
|
# optimization = "none"
|
||
|
|
||
|
## Maximum number of registers the optimizer is allowed to insert between
|
||
|
## non-consecutive registers to save requests.
|
||
|
## This option is only used for the 'max_insert' optimization strategy and
|
||
|
## effectively denotes the hole size between registers to fill.
|
||
|
# optimization_max_register_fill = 50
|
||
|
|
||
|
## Define a metric produced by the requests to the device
|
||
|
## Multiple of those metrics can be defined. The referenced registers will
|
||
|
## be collated into requests send to the device
|
||
|
[[inputs.modbus.metric]]
|
||
|
## ID of the modbus slave device to query
|
||
|
## If you need to query multiple slave-devices, create several "metric" definitions.
|
||
|
slave_id = 1
|
||
|
|
||
|
## Byte order of the data
|
||
|
## |---ABCD -- Big Endian (Motorola)
|
||
|
## |---DCBA -- Little Endian (Intel)
|
||
|
## |---BADC -- Big Endian with byte swap
|
||
|
## |---CDAB -- Little Endian with byte swap
|
||
|
# byte_order = "ABCD"
|
||
|
|
||
|
## Name of the measurement
|
||
|
# measurement = "modbus"
|
||
|
|
||
|
## Field definitions
|
||
|
## register - type of the modbus register, can be "coil", "discrete",
|
||
|
## "holding" or "input". Defaults to "holding".
|
||
|
## address - address of the register to query. For coil and discrete inputs this is the bit address.
|
||
|
## name - field name
|
||
|
## type *1 - type of the modbus field, can be
|
||
|
## BIT (single bit of a register)
|
||
|
## INT8L, INT8H, UINT8L, UINT8H (low and high byte variants)
|
||
|
## INT16, UINT16, INT32, UINT32, INT64, UINT64 and
|
||
|
## FLOAT16, FLOAT32, FLOAT64 (IEEE 754 binary representation)
|
||
|
## STRING (byte-sequence converted to string)
|
||
|
## length *1 - (optional) number of registers, ONLY valid for STRING type
|
||
|
## bit *1,2 - (optional) bit of the register, ONLY valid for BIT type
|
||
|
## scale *1,3 - (optional) factor to scale the variable with
|
||
|
## output *2,3 - (optional) type of resulting field, can be INT64, UINT64 or FLOAT64. Defaults to FLOAT64 if
|
||
|
## "scale" is provided and to the input "type" class otherwise (i.e. INT* -> INT64, etc).
|
||
|
##
|
||
|
## *1: These fields are ignored for both "coil" and "discrete"-input type of registers.
|
||
|
## *2: This field can only be "UINT16" or "BOOL" if specified for both "coil"
|
||
|
## and "discrete"-input type of registers. By default the fields are
|
||
|
## output as zero or one in UINT16 format unless "BOOL" is used.
|
||
|
## *3: These fields cannot be used with "STRING"-type fields.
|
||
|
fields = [
|
||
|
{ register="coil", address=0, name="door_open"},
|
||
|
{ register="coil", address=1, name="status_ok"},
|
||
|
{ register="holding", address=0, name="voltage", type="INT16" },
|
||
|
{ address=1, name="current", type="INT32", scale=0.001 },
|
||
|
{ address=5, name="energy", type="FLOAT32", scale=0.001 },
|
||
|
{ address=7, name="frequency", type="UINT32", scale=0.1 },
|
||
|
{ address=8, name="power_factor", type="INT64", scale=0.01 },
|
||
|
{ address=9, name="firmware", type="STRING", length=8 },
|
||
|
]
|
||
|
|
||
|
## Tags assigned to the metric
|
||
|
# [inputs.modbus.metric.tags]
|
||
|
# machine = "impresser"
|
||
|
# location = "main building"
|
||
|
|
||
|
## RS485 specific settings. Only take effect for serial controllers.
|
||
|
## Note: This has to be at the end of the modbus configuration due to
|
||
|
## TOML constraints.
|
||
|
# [inputs.modbus.rs485]
|
||
|
## Delay RTS prior to sending
|
||
|
# delay_rts_before_send = "0ms"
|
||
|
## Delay RTS after to sending
|
||
|
# delay_rts_after_send = "0ms"
|
||
|
## Pull RTS line to high during sending
|
||
|
# rts_high_during_send = false
|
||
|
## Pull RTS line to high after sending
|
||
|
# rts_high_after_send = false
|
||
|
## Enabling receiving (Rx) during transmission (Tx)
|
||
|
# rx_during_tx = false
|
||
|
|
||
|
## Enable workarounds required by some devices to work correctly
|
||
|
# [inputs.modbus.workarounds]
|
||
|
## Pause after connect delays the first request by the specified time.
|
||
|
## This might be necessary for (slow) devices.
|
||
|
# pause_after_connect = "0ms"
|
||
|
|
||
|
## Pause between read requests sent to the device.
|
||
|
## This might be necessary for (slow) serial devices.
|
||
|
# pause_between_requests = "0ms"
|
||
|
|
||
|
## Close the connection after every gather cycle.
|
||
|
## Usually the plugin closes the connection after a certain idle-timeout,
|
||
|
## however, if you query a device with limited simultaneous connectivity
|
||
|
## (e.g. serial devices) from multiple instances you might want to only
|
||
|
## stay connected during gather and disconnect afterwards.
|
||
|
# close_connection_after_gather = false
|
||
|
|
||
|
## Force the plugin to read each field in a separate request.
|
||
|
## This might be necessary for devices not conforming to the spec,
|
||
|
## see https://github.com/influxdata/telegraf/issues/12071.
|
||
|
# one_request_per_field = false
|
||
|
|
||
|
## Enforce the starting address to be zero for the first request on
|
||
|
## coil registers. This is necessary for some devices see
|
||
|
## https://github.com/influxdata/telegraf/issues/8905
|
||
|
# read_coils_starting_at_zero = false
|
||
|
|
||
|
## String byte-location in registers AFTER byte-order conversion
|
||
|
## Some device (e.g. EM340) place the string byte in only the upper or
|
||
|
## lower byte location of a register see
|
||
|
## https://github.com/influxdata/telegraf/issues/14748
|
||
|
## Available settings:
|
||
|
## lower -- use only lower byte of the register i.e. 00XX 00XX 00XX 00XX
|
||
|
## upper -- use only upper byte of the register i.e. XX00 XX00 XX00 XX00
|
||
|
## By default both bytes of the register are used i.e. XXXX XXXX.
|
||
|
# string_register_location = ""
|
||
|
```
|
||
|
|
||
|
## Notes
|
||
|
|
||
|
You can debug Modbus connection issues by enabling `debug_connection`. To see
|
||
|
those debug messages, Telegraf has to be started with debugging enabled
|
||
|
(i.e. with the `--debug` option). Please be aware that connection tracing will
|
||
|
produce a lot of messages and should __NOT__ be used in production environments.
|
||
|
|
||
|
Please use `pause_after_connect` / `pause_between_requests` with care. Ensure
|
||
|
the total gather time, including the pause(s), does not exceed the configured
|
||
|
collection interval. Note that pauses add up if multiple requests are sent!
|
||
|
|
||
|
## Configuration styles
|
||
|
|
||
|
The modbus plugin supports multiple configuration styles that can be set using
|
||
|
the `configuration_type` setting. The different styles are described
|
||
|
below. Please note that styles cannot be mixed, i.e. only the settings belonging
|
||
|
to the configured `configuration_type` are used for constructing _modbus_
|
||
|
requests and creation of metrics.
|
||
|
|
||
|
Directly jump to the styles:
|
||
|
|
||
|
- [original / register plugin style](#register-configuration-style)
|
||
|
- [per-request style](#request-configuration-style)
|
||
|
- [per-metrict style](#metric-configuration-style)
|
||
|
|
||
|
---
|
||
|
|
||
|
### `register` configuration style
|
||
|
|
||
|
This is the original style used by this plugin. It allows a per-register
|
||
|
configuration for a single slave-device.
|
||
|
|
||
|
> [!NOTE]
|
||
|
> For legacy reasons this configuration style is not completely consistent with the other styles.
|
||
|
|
||
|
#### Usage of `data_type`
|
||
|
|
||
|
The field `data_type` defines the representation of the data value on input from
|
||
|
the modbus registers. The input values are then converted from the given
|
||
|
`data_type` to a type that is appropriate when sending the value to the output
|
||
|
plugin. These output types are usually an integer or floating-point-number. The
|
||
|
size of the output type is assumed to be large enough for all supported input
|
||
|
types. The mapping from the input type to the output type is fixed and cannot
|
||
|
be configured.
|
||
|
|
||
|
##### Booleans: `BOOL`
|
||
|
|
||
|
This type is only valid for _coil_ and _discrete_ registers. The value will be
|
||
|
`true` if the register has a non-zero (ON) value and `false` otherwise.
|
||
|
|
||
|
##### Integers: `INT8L`, `INT8H`, `UINT8L`, `UINT8H`
|
||
|
|
||
|
These types are used for 8-bit integer values. Select the one that matches your
|
||
|
modbus data source. The `L` and `H` suffix denotes the low- and high byte of
|
||
|
the register respectively.
|
||
|
|
||
|
##### Integers: `INT16`, `UINT16`, `INT32`, `UINT32`, `INT64`, `UINT64`
|
||
|
|
||
|
These types are used for integer input values. Select the one that matches your
|
||
|
modbus data source. For _coil_ and _discrete_ registers only `UINT16` is valid.
|
||
|
|
||
|
##### Floating Point: `FLOAT16-IEEE`, `FLOAT32-IEEE`, `FLOAT64-IEEE`
|
||
|
|
||
|
Use these types if your modbus registers contain a value that is encoded in this
|
||
|
format. These types always include the sign, therefore no variant exists.
|
||
|
|
||
|
##### Fixed Point: `FIXED`, `UFIXED`
|
||
|
|
||
|
These types are handled as an integer type on input, but are converted to
|
||
|
floating point representation for further processing (e.g. scaling). Use one of
|
||
|
these types when the input value is a decimal fixed point representation of a
|
||
|
non-integer value.
|
||
|
|
||
|
Select the type `UFIXED` when the input type is declared to hold unsigned
|
||
|
integer values, which cannot be negative. The documentation of your modbus
|
||
|
device should indicate this by a term like 'uint16 containing fixed-point
|
||
|
representation with N decimal places'.
|
||
|
|
||
|
Select the type `FIXED` when the input type is declared to hold signed integer
|
||
|
values. Your documentation of the modbus device should indicate this with a term
|
||
|
like 'int32 containing fixed-point representation with N decimal places'.
|
||
|
|
||
|
##### String: `STRING`
|
||
|
|
||
|
This type is used to query the number of registers specified in the `address`
|
||
|
setting and convert the byte-sequence to a string. Please note, if the
|
||
|
byte-sequence contains a `null` byte, the string is truncated at this position.
|
||
|
You cannot use the `scale` setting for string fields.
|
||
|
|
||
|
##### Bit: `BIT`
|
||
|
|
||
|
This type is used to query a single bit of a register specified in the `address`
|
||
|
setting and convert the value to an unsigned integer. This type __requires__ the
|
||
|
`bit` setting to be specified.
|
||
|
|
||
|
---
|
||
|
|
||
|
### `request` configuration style
|
||
|
|
||
|
This style can be used to specify the modbus requests directly. It enables
|
||
|
specifying multiple `[[inputs.modbus.request]]` sections including multiple
|
||
|
slave-devices. This way, _modbus_ gateway devices can be queried. Please note
|
||
|
that _requests_ might be split for non-consecutive addresses. If you want to
|
||
|
avoid this behavior please add _fields_ with the `omit` flag set filling the
|
||
|
gaps between addresses.
|
||
|
|
||
|
#### Slave device
|
||
|
|
||
|
You can use the `slave_id` setting to specify the ID of the slave device to
|
||
|
query. It should be specified for each request, otherwise it defaults to
|
||
|
zero. Please note, only one `slave_id` can be specified per request.
|
||
|
|
||
|
#### Byte order of the register
|
||
|
|
||
|
The `byte_order` setting specifies the byte and word-order of the registers. It
|
||
|
can be set to `ABCD` for _big endian (Motorola)_ or `DCBA` for _little endian
|
||
|
(Intel)_ format as well as `BADC` and `CDAB` for _big endian_ or _little endian_
|
||
|
with _byte swap_.
|
||
|
|
||
|
#### Register type
|
||
|
|
||
|
The `register` setting specifies the modbus register-set to query and can be set
|
||
|
to `coil`, `discrete`, `holding` or `input`.
|
||
|
|
||
|
#### Per-request measurement setting
|
||
|
|
||
|
You can specify the name of the measurement for the following field definitions
|
||
|
using the `measurement` setting. If the setting is omitted `modbus` is
|
||
|
used. Furthermore, the measurement value can be overridden by each field
|
||
|
individually.
|
||
|
|
||
|
#### Optimization setting
|
||
|
|
||
|
__Please only use request optimization if you do understand the implications!__
|
||
|
The `optimization` setting can be used to optimize the actual requests sent to
|
||
|
the device. The following algorithms are available
|
||
|
|
||
|
##### `none` (_default_)
|
||
|
|
||
|
Do not perform any optimization. Please note that the requests are still obeying
|
||
|
the maximum request sizes. Furthermore, completely empty requests, i.e. all
|
||
|
fields specify `omit=true`, are removed. Otherwise, the requests are sent as
|
||
|
specified by the user including request of omitted fields. This setting should
|
||
|
be used if you want full control over the requests e.g. to accommodate for
|
||
|
device constraints.
|
||
|
|
||
|
##### `shrink`
|
||
|
|
||
|
This optimization allows to remove leading and trailing fields from requests if
|
||
|
those fields are omitted. This can shrink the request number and sizes in cases
|
||
|
where you specify large amounts of omitted fields, e.g. for documentation
|
||
|
purposes.
|
||
|
|
||
|
##### `rearrange`
|
||
|
|
||
|
Requests are processed similar to `shrink` but the request boundaries are
|
||
|
rearranged such that usually less registers are being read while keeping the
|
||
|
number of requests. This optimization algorithm only works on consecutive
|
||
|
address ranges and respects user-defined gaps in the field addresses.
|
||
|
|
||
|
__Please note:__ This optimization might take long in case of many
|
||
|
non-consecutive, non-omitted fields!
|
||
|
|
||
|
##### `aggressive`
|
||
|
|
||
|
Requests are processed similar to `rearrange` but user-defined gaps in the field
|
||
|
addresses are filled automatically. This usually reduces the number of requests,
|
||
|
but will increase the number of registers read due to larger requests.
|
||
|
This algorithm might be useful if you only want to specify the fields you are
|
||
|
interested in but want to minimize the number of requests sent to the device.
|
||
|
|
||
|
__Please note:__ This optimization might take long in case of many
|
||
|
non-consecutive, non-omitted fields!
|
||
|
|
||
|
##### `max_insert`
|
||
|
|
||
|
Fields are assigned to the same request as long as the hole between the fields
|
||
|
do not exceed the maximum fill size given in `optimization_max_register_fill`.
|
||
|
User-defined omitted fields are ignored and interpreted as holes, so the best
|
||
|
practice is to not manually insert omitted fields for this optimizer. This
|
||
|
allows to specify only actually used fields and let the optimizer figure out
|
||
|
the request organization which can dramatically improve query time. The
|
||
|
trade-off here is between the cost of reading additional registers trashed
|
||
|
later and the cost of many requests.
|
||
|
|
||
|
__Please note:__ The optimal value for `optimization_max_register_fill` depends
|
||
|
on the network and the queried device. It is hence recommended to test several
|
||
|
values and assess performance in order to find the best value. Use the
|
||
|
`--test --debug` flags to monitor how may requests are sent and the number of
|
||
|
touched registers.
|
||
|
|
||
|
#### Field definitions
|
||
|
|
||
|
Each `request` can contain a list of fields to collect from the modbus device.
|
||
|
|
||
|
##### address
|
||
|
|
||
|
A field is identified by an `address` that reflects the modbus register
|
||
|
address. You can usually find the address values for the different data-points
|
||
|
in the datasheet of your modbus device. This is a mandatory setting.
|
||
|
|
||
|
For _coil_ and _discrete input_ registers this setting specifies the __bit__
|
||
|
containing the value of the field.
|
||
|
|
||
|
##### name
|
||
|
|
||
|
Using the `name` setting you can specify the field-name in the metric as output
|
||
|
by the plugin. This setting is ignored if the field's `omit` is set to `true`
|
||
|
and can be omitted in this case.
|
||
|
|
||
|
__Please note:__ There cannot be multiple fields with the same `name` in one
|
||
|
metric identified by `measurement`, `slave_id` and `register`.
|
||
|
|
||
|
##### register datatype
|
||
|
|
||
|
The `type` setting specifies the datatype of the modbus register and can be
|
||
|
set to `INT8L`, `INT8H`, `UINT8L`, `UINT8H` where `L` is the lower byte of the
|
||
|
register and `H` is the higher byte.
|
||
|
Furthermore, the types `INT16`, `UINT16`, `INT32`, `UINT32`, `INT64` or `UINT64`
|
||
|
for integer types or `FLOAT16`, `FLOAT32` and `FLOAT64` for IEEE 754 binary
|
||
|
representations of floating point values exist. `FLOAT16` denotes a
|
||
|
half-precision float with a 16-bit representation.
|
||
|
Usually the datatype of the register is listed in the datasheet of your modbus
|
||
|
device in relation to the `address` described above.
|
||
|
|
||
|
The `STRING` datatype is special in that it requires the `length` setting to
|
||
|
be specified containing the length (in terms of number of registers) containing
|
||
|
the string. The returned byte-sequence is interpreted as string and truncated
|
||
|
to the first `null` byte found if any. The `scale` and `output` setting cannot
|
||
|
be used for this `type`.
|
||
|
|
||
|
This setting is ignored if the field's `omit` is set to `true` or if the
|
||
|
`register` type is a bit-type (`coil` or `discrete`) and can be omitted in
|
||
|
these cases.
|
||
|
|
||
|
##### scaling
|
||
|
|
||
|
You can use the `scale` setting to scale the register values, e.g. if the
|
||
|
register contains a fix-point values in `UINT32` format with two decimal places
|
||
|
for example. To convert the read register value to the actual value you can set
|
||
|
the `scale=0.01`. The scale is used as a factor e.g. `field_value * scale`.
|
||
|
|
||
|
This setting is ignored if the field's `omit` is set to `true` or if the
|
||
|
`register` type is a bit-type (`coil` or `discrete`) and can be omitted in these
|
||
|
cases.
|
||
|
|
||
|
__Please note:__ The resulting field-type will be set to `FLOAT64` if no output
|
||
|
format is specified.
|
||
|
|
||
|
##### output datatype
|
||
|
|
||
|
Using the `output` setting you can explicitly specify the output
|
||
|
field-datatype. The `output` type can be `INT64`, `UINT64` or `FLOAT64`. If not
|
||
|
set explicitly, the output type is guessed as follows: If `scale` is set to a
|
||
|
non-zero value, the output type is `FLOAT64`. Otherwise, the output type
|
||
|
corresponds to the register datatype _class_, i.e. `INT*` will result in
|
||
|
`INT64`, `UINT*` in `UINT64` and `FLOAT*` in `FLOAT64`.
|
||
|
|
||
|
This setting is ignored if the field's `omit` is set to `true` and can be
|
||
|
omitted. In case the `register` type is a bit-type (`coil` or `discrete`) only
|
||
|
`UINT16` or `BOOL` are valid with the former being the default if omitted.
|
||
|
For `coil` and `discrete` registers the field-value is output as zero or one in
|
||
|
`UINT16` format or as `true` and `false` in `BOOL` format.
|
||
|
|
||
|
#### per-field measurement setting
|
||
|
|
||
|
The `measurement` setting can be used to override the measurement name on a
|
||
|
per-field basis. This might be useful if you want to split the fields in one
|
||
|
request to multiple measurements. If not specified, the value specified in the
|
||
|
[`request` section](#per-request-measurement-setting) or, if also omitted,
|
||
|
`modbus` is used.
|
||
|
|
||
|
This setting is ignored if the field's `omit` is set to `true` and can be
|
||
|
omitted in this case.
|
||
|
|
||
|
#### omitting a field
|
||
|
|
||
|
When specifying `omit=true`, the corresponding field will be ignored when
|
||
|
collecting the metric but is taken into account when constructing the modbus
|
||
|
requests. This way, you can fill "holes" in the addresses to construct
|
||
|
consecutive address ranges resulting in a single request. Using a single modbus
|
||
|
request can be beneficial as the values are all collected at the same point in
|
||
|
time.
|
||
|
|
||
|
#### Tags definitions
|
||
|
|
||
|
Each `request` can be accompanied by tags valid for this request.
|
||
|
|
||
|
__Please note:__ These tags take precedence over predefined tags such as `name`,
|
||
|
`type` or `slave_id`.
|
||
|
|
||
|
---
|
||
|
|
||
|
### `metric` configuration style
|
||
|
|
||
|
This style can be used to specify the desired metrics directly instead of
|
||
|
focusing on the modbus view. Multiple `[[inputs.modbus.metric]]` sections
|
||
|
including multiple slave-devices can be specified. This way, _modbus_ gateway
|
||
|
devices can be queried. The plugin automatically collects registers across
|
||
|
the specified metrics, groups them per slave and register-type and (optionally)
|
||
|
optimizes the resulting requests for non-consecutive addresses.
|
||
|
|
||
|
#### Slave device
|
||
|
|
||
|
You can use the `slave_id` setting to specify the ID of the slave device to
|
||
|
query. It should be specified for each metric section, otherwise it defaults to
|
||
|
zero. Please note, only one `slave_id` can be specified per metric section.
|
||
|
|
||
|
#### Byte order of the registers
|
||
|
|
||
|
The `byte_order` setting specifies the byte and word-order of the registers. It
|
||
|
can be set to `ABCD` for _big endian (Motorola)_ or `DCBA` for _little endian
|
||
|
(Intel)_ format as well as `BADC` and `CDAB` for _big endian_ or _little endian_
|
||
|
with _byte swap_.
|
||
|
|
||
|
#### Measurement name
|
||
|
|
||
|
You can specify the name of the measurement for the fields defined in the
|
||
|
given section using the `measurement` setting. If the setting is omitted
|
||
|
`modbus` is used.
|
||
|
|
||
|
#### Optimization setting
|
||
|
|
||
|
__Please only use request optimization if you do understand the implications!__
|
||
|
The `optimization` setting can specified globally, i.e. __NOT__ per metric
|
||
|
section, and is used to optimize the actual requests sent to the device. Here,
|
||
|
the optimization is applied across _all metric sections_! The following
|
||
|
algorithms are available
|
||
|
|
||
|
##### `none` (_default_)
|
||
|
|
||
|
Do not perform any optimization. Please note that consecutive registers are
|
||
|
still grouped into one requests while obeying the maximum request sizes. This
|
||
|
setting should be used if you want to touch as less registers as possible at
|
||
|
the cost of more requests sent to the device.
|
||
|
|
||
|
##### `max_insert`
|
||
|
|
||
|
Fields are assigned to the same request as long as the hole between the touched
|
||
|
registers does not exceed the maximum fill size given via
|
||
|
`optimization_max_register_fill`. This optimization might lead to a drastically
|
||
|
reduced request number and thus an improved query time. The trade-off here is
|
||
|
between the cost of reading additional registers trashed later and the cost of
|
||
|
many requests.
|
||
|
|
||
|
__Please note:__ The optimal value for `optimization_max_register_fill` depends
|
||
|
on the network and the queried device. It is hence recommended to test several
|
||
|
values and assess performance in order to find the best value. Use the
|
||
|
`--test --debug` flags to monitor how may requests are sent and the number of
|
||
|
touched registers.
|
||
|
|
||
|
#### Field definitions
|
||
|
|
||
|
Each `metric` can contain a list of fields to collect from the modbus device.
|
||
|
The specified fields directly corresponds to the fields of the resulting metric.
|
||
|
|
||
|
##### register
|
||
|
|
||
|
The `register` setting specifies the modbus register-set to query and can be set
|
||
|
to `coil`, `discrete`, `holding` or `input`.
|
||
|
|
||
|
##### address
|
||
|
|
||
|
A field is identified by an `address` that reflects the modbus register
|
||
|
address. You can usually find the address values for the different data-points
|
||
|
in the datasheet of your modbus device. This is a mandatory setting.
|
||
|
|
||
|
For _coil_ and _discrete input_ registers this setting specifies the __bit__
|
||
|
containing the value of the field.
|
||
|
|
||
|
##### name
|
||
|
|
||
|
Using the `name` setting you can specify the field-name in the metric as output
|
||
|
by the plugin.
|
||
|
|
||
|
__Please note:__ There cannot be multiple fields with the same `name` in one
|
||
|
metric identified by `measurement`, `slave_id`, `register` and tag-set.
|
||
|
|
||
|
##### register datatype
|
||
|
|
||
|
The `type` setting specifies the datatype of the modbus register and can be
|
||
|
set to `INT8L`, `INT8H`, `UINT8L`, `UINT8H` where `L` is the lower byte of the
|
||
|
register and `H` is the higher byte.
|
||
|
Furthermore, the types `INT16`, `UINT16`, `INT32`, `UINT32`, `INT64` or `UINT64`
|
||
|
for integer types or `FLOAT16`, `FLOAT32` and `FLOAT64` for IEEE 754 binary
|
||
|
representations of floating point values exist. `FLOAT16` denotes a
|
||
|
half-precision float with a 16-bit representation.
|
||
|
Usually the datatype of the register is listed in the datasheet of your modbus
|
||
|
device in relation to the `address` described above.
|
||
|
|
||
|
The `STRING` datatype is special in that it requires the `length` setting to
|
||
|
be specified containing the length (in terms of number of registers) containing
|
||
|
the string. The returned byte-sequence is interpreted as string and truncated
|
||
|
to the first `null` byte found if any. The `scale` and `output` setting cannot
|
||
|
be used for this `type`.
|
||
|
|
||
|
This setting is ignored if the `register` is a bit-type (`coil` or `discrete`)
|
||
|
and can be omitted in these cases.
|
||
|
|
||
|
##### scaling
|
||
|
|
||
|
You can use the `scale` setting to scale the register values, e.g. if the
|
||
|
register contains a fix-point values in `UINT32` format with two decimal places
|
||
|
for example. To convert the read register value to the actual value you can set
|
||
|
the `scale=0.01`. The scale is used as a factor e.g. `field_value * scale`.
|
||
|
|
||
|
This setting is ignored if the `register` is a bit-type (`coil` or `discrete`)
|
||
|
and can be omitted in these cases.
|
||
|
|
||
|
__Please note:__ The resulting field-type will be set to `FLOAT64` if no output
|
||
|
format is specified.
|
||
|
|
||
|
##### output datatype
|
||
|
|
||
|
Using the `output` setting you can explicitly specify the output
|
||
|
field-datatype. The `output` type can be `INT64`, `UINT64` or `FLOAT64`. If not
|
||
|
set explicitly, the output type is guessed as follows: If `scale` is set to a
|
||
|
non-zero value, the output type is `FLOAT64`. Otherwise, the output type
|
||
|
corresponds to the register datatype _class_, i.e. `INT*` will result in
|
||
|
`INT64`, `UINT*` in `UINT64` and `FLOAT*` in `FLOAT64`.
|
||
|
|
||
|
In case the `register` is a bit-type (`coil` or `discrete`) only `UINT16` or
|
||
|
`BOOL` are valid with the former being the default if omitted. For `coil` and
|
||
|
`discrete` registers the field-value is output as zero or one in `UINT16` format
|
||
|
or as `true` and `false` in `BOOL` format.
|
||
|
|
||
|
#### Tags definitions
|
||
|
|
||
|
Each `metric` can be accompanied by a set of tag. These tags directly correspond
|
||
|
to the tags of the resulting metric.
|
||
|
|
||
|
__Please note:__ These tags take precedence over predefined tags such as `name`,
|
||
|
`type` or `slave_id`.
|
||
|
|
||
|
---
|
||
|
|
||
|
## Troubleshooting
|
||
|
|
||
|
### Strange data
|
||
|
|
||
|
Modbus documentation is often a mess. People confuse memory-address (starts at
|
||
|
one) and register address (starts at zero) or are unsure about the word-order
|
||
|
used. Furthermore, there are some non-standard implementations that also swap
|
||
|
the bytes within the register word (16-bit).
|
||
|
|
||
|
If you get an error or don't get the expected values from your device, you can
|
||
|
try the following steps (assuming a 32-bit value).
|
||
|
|
||
|
If you are using a serial device and get a `permission denied` error, check the
|
||
|
permissions of your serial device and change them accordingly.
|
||
|
|
||
|
In case you get an `exception '2' (illegal data address)` error you might try to
|
||
|
offset your `address` entries by minus one as it is very likely that there is
|
||
|
confusion between memory and register addresses.
|
||
|
|
||
|
If you see strange values, the `byte_order` might be wrong. You can either probe
|
||
|
all combinations (`ABCD`, `CDBA`, `BADC` or `DCBA`) or set `byte_order="ABCD"
|
||
|
data_type="UINT32"` and use the resulting value(s) in an online converter like
|
||
|
[this][online-converter]. This especially makes sense if you don't want to mess
|
||
|
with the device, deal with 64-bit values and/or don't know the `data_type` of
|
||
|
your register (e.g. fix-point floating values vs. IEEE floating point).
|
||
|
|
||
|
If your data still looks corrupted, please post your configuration, error
|
||
|
message and/or the output of `byte_order="ABCD" data_type="UINT32"` to one of
|
||
|
the telegraf support channels (forum, slack or as an issue). If nothing helps,
|
||
|
please post your configuration, error message and/or the output of
|
||
|
`byte_order="ABCD" data_type="UINT32"` to one of the telegraf support channels
|
||
|
(forum, slack or as an issue).
|
||
|
|
||
|
[online-converter]: https://www.scadacore.com/tools/programming-calculators/online-hex-converter/
|
||
|
|
||
|
### Workarounds
|
||
|
|
||
|
Some Modbus devices need special read characteristics when reading data and will
|
||
|
fail otherwise. For example, some serial devices need a pause between register
|
||
|
read requests. Others might only support a limited number of simultaneously
|
||
|
connected devices, like serial devices or some ModbusTCP devices. In case you
|
||
|
need to access those devices in parallel you might want to disconnect
|
||
|
immediately after the plugin finishes reading.
|
||
|
|
||
|
To enable this plugin to also handle those "special" devices, there is the
|
||
|
`workarounds` configuration option. In case your documentation states certain
|
||
|
read requirements or you get read timeouts or other read errors, you might want
|
||
|
to try one or more workaround options. If you find that other/more workarounds
|
||
|
are required for your device, please let us know.
|
||
|
|
||
|
In case your device needs a workaround that is not yet implemented, please open
|
||
|
an issue or submit a pull-request.
|
||
|
|
||
|
## Metrics
|
||
|
|
||
|
The plugin reads the configured registers and constructs metrics based on the
|
||
|
specified configuration. There is no predefined metric format.
|
||
|
|
||
|
## Example Output
|
||
|
|
||
|
```text
|
||
|
modbus,name=device,slave_id=1,type=holding_register energy=3254.5,power=23.5,frequency=49,97 1701777274026591864
|
||
|
```
|