# UPSD Input Plugin
This plugin reads data of one or more Uninterruptible Power Supplies
from an `upsd` daemon using its NUT network protocol.
## Requirements
`upsd` should be installed and it's daemon should be running.
## Global configuration options <!-- @/docs/includes/plugin_config.md -->
In addition to the plugin-specific configuration settings, plugins support
additional global and plugin configuration settings. These settings are used to
modify metrics, tags, and field or create aliases and configure ordering, etc.
See the [CONFIGURATION.md][CONFIGURATION.md] for more details.
[CONFIGURATION.md]: ../../../docs/CONFIGURATION.md#plugins
## Configuration
```toml @sample.conf
# Monitor UPSes connected via Network UPS Tools
[[inputs.upsd]]
## A running NUT server to connect to.
## IPv6 addresses must be enclosed in brackets (e.g. "[::1]")
# server = "127.0.0.1"
# port = 3493
# username = "user"
# password = "password"
## Force parsing numbers as floats
## It is highly recommended to enable this setting to parse numbers
## consistently as floats to avoid database conflicts where some numbers are
## parsed as integers and others as floats.
# force_float = false
## Collect additional fields if they are available for the UPS
## The fields need to be specified as NUT variable names, see
## https://networkupstools.org/docs/developer-guide.chunked/apas02.html
## Wildcards are accepted.
# additional_fields = []
## Dump information for debugging
## Allows to print the raw variables (and corresponding types) as received
## from the NUT server ONCE for each UPS.
## Please attach this information when reporting issues!
# log_level = "trace"
```
## Pitfalls
Please note that field types are automatically determined based on the values.
Especially the strings `enabled` and `disabled` are automatically converted to
`boolean` values. This might lead to trouble for fields that can contain
non-binary values like `enabled`, `disabled` and `muted` as the output field
will be `boolean` for the first two values but `string` for the latter. To
convert `enabled` and `disabled` values back to `string` for those fields, use
the [enum processor][enum_processor] with
```toml
[[processors.enum]]
[[processors.enum.mapping]]
field = "ups_beeper_status"
[processors.enum.mapping.value_mappings]
true = "enabled"
false = "disabled"
```
Alternatively, you can also map the non-binary value to a `boolean`.
[enum_processor]: ../../processors/enum/README.md
## Metrics
This implementation tries to maintain compatibility with the apcupsd metrics:
- upsd
- tags:
- serial
- ups_name
- model
- fields:
- status_flags ([status-bits][rfc9271-sec5.1])
- input_voltage
- load_percent
- battery_charge_percent
- time_left_ns
- output_voltage
- internal_temp
- battery_voltage
- input_frequency
- battery_date
- nominal_input_voltage
- nominal_battery_voltage
- nominal_power
- firmware
With the exception of:
- tags:
- status (string representing the set status_flags)
- fields:
- time_on_battery_ns
[rfc9271-sec5.1]: https://www.rfc-editor.org/rfc/rfc9271.html#section-5.1
## Example Output
```text
upsd,serial=AS1231515,ups_name=name1 load_percent=9.7,time_left_ns=9800000,output_voltage=230.4,internal_temp=32.4,battery_voltage=27.4,input_frequency=50.2,input_voltage=230.4,battery_charge_percent=100,status_flags=8i 1490035922000000000
```